XGN-12 environmentally friendly gas insulated switchgear is a new generation of switch products independently developed by Jinneng. Its internal use of micro-positive pressure dry N₂ gas as insulation medium,instead SF6 gas.

 

● Insulation Medium: Dry Air or Nitrogen, with GWP≈1 (SF₆ GWP=23500), zero greenhouse effect, non-toxic and non-flammable.

● Core Structure: We put all high-voltage live parts (busbars, vacuum circuit breakers/load switches, three-position switches, transformers) in a stainless steel gas tank filled with slight positive pressure (approx. 0.02–0.05 MPa) environmentally friendly gas.

● Arc Extinguishing Method: Adopts vacuum interruption with separated insulation and arc-quenching functions, ensuring stable performance and long service life.

● Protection Degree: IP67 for the gas tank, IP54/IP65 for the whole cabinet, fully dustproof, moisture-proof, anti-condensation, anti-corrosion and protected against small animals.

 

Model Meaning

 

product-1471-204

 

① Product model

② Rated voltage (kV)

③ Unit cabinet scheme code

④ Rated current (A)

⑤ Rated short-time withstand current (kA)

 

Technical parameters

 

Item

Unit

Parameter

Rated voltage

kV

12

Rated frequency

Hz

50

Rated current

A

630/1250/2500/3150

Rated

insulation

level

1min power frequency withstand voltage

phase to earth

kV

42

contact gap

kV

48

Control & Auxiliary Circuits

kV

2

1min Lightning Impulse Withstand Voltage

phase to earth

kV

75

contact gap

kV

85

Rated short-time withstand current

kA/s

25,31.5,40/4

Rated peak withstand current

kA

63,80,100

Rated short-circuit breaking current

kA

25,31.5,40

Rated short-circuit closing current

kA

63,80,100

Circuit breaker life

Time

30

Rated operating sequence

/

O-0.3s-CO-180s-CO

Mechanical life

Circuit breaker

Times

20000

lsolation/ground switch

Times

5000

Loop

resistance

1250A

μΩ

≤120

2500A

μΩ

≤80

3150A

μΩ

≤80

Rated filling pressure (gauge pressure at 20℃)

MPa

0.02

Annual gas leakage rate

Years

≤0.01%

Insulating gas

/

N2

Class of

protection

Compartment

/

IP20

Gas box

/

IP67

Cabinet

/

IP41

Cabinet Impact Resistance (IK class)

/

Ik10

Arc fault test (fault current/duration)

kA/s

31.5/1,40/0.5

 

Usage conditions

 

1. The ambient air temperature does not exceed 40°C, the 24-hour average does not exceed 35 ℃, and the minimum air temperature does not exceed 40°C

2. Altitude: ≤2000m

3. Humidity Relative humidity: daily average is not more than 95%, monthly average is not more than 90%; Water vapor pressure: the daily average is not more than 2.2Kpa, the monthly average is not more than 1.8Kpa

4. Seismic intensity: no more than 8 degrees, horizontal acceleration ≤0.4g, vertical acceleration ≤0.5g

5. Special conditions of use: When the switch cabinet is not normal use conditions, the user should negotiate with the manufacturer

 

Quality control

 

Strictly running quality control of XGN-12 SF6 gas insulated switchgear according to ISO9001, from supplier quality assurance-Incoming material -Incoming inspection-Qualified-Production-Process quality control-Final inspection-Qualified-In and out of storage-After-sales quality control

Contact now

product-1200-628

Hot Tags: xgn-12 sf6 gas insulated switchgear, China xgn-12 sf6 gas insulated switchgear manufacturers, suppliers, factory, gis rmu, gis switchgear, gis ring main unit, ring switch, inflatable ring main unit, rm6 ring main unit

Next: No Information →
Send Inquiry

(0/10)

clearall