XGN-12 SF6 Gas Insulated Switchgear
✅Eco-friendly Insulation Solution,no SF₆ gas
✅Fully Sealed Structure,IP67
✅Intelligent Monitoring System
✅Compact Design,save 50% room
✅Long Service Life & Maintenance-Free
- Product Introduction
XGN-12 environmentally friendly gas insulated switchgear is a new generation of switch products independently developed by Jinneng. Its internal use of micro-positive pressure dry N₂ gas as insulation medium,instead SF6 gas.
● Insulation Medium: Dry Air or Nitrogen, with GWP≈1 (SF₆ GWP=23500), zero greenhouse effect, non-toxic and non-flammable.
● Core Structure: We put all high-voltage live parts (busbars, vacuum circuit breakers/load switches, three-position switches, transformers) in a stainless steel gas tank filled with slight positive pressure (approx. 0.02–0.05 MPa) environmentally friendly gas.
● Arc Extinguishing Method: Adopts vacuum interruption with separated insulation and arc-quenching functions, ensuring stable performance and long service life.
● Protection Degree: IP67 for the gas tank, IP54/IP65 for the whole cabinet, fully dustproof, moisture-proof, anti-condensation, anti-corrosion and protected against small animals.
Model Meaning

① Product model
② Rated voltage (kV)
③ Unit cabinet scheme code
④ Rated current (A)
⑤ Rated short-time withstand current (kA)
Technical parameters
|
Item |
Unit |
Parameter |
||
|
Rated voltage |
kV |
12 |
||
|
Rated frequency |
Hz |
50 |
||
|
Rated current |
A |
630/1250/2500/3150 |
||
|
Rated insulation level |
1min power frequency withstand voltage |
phase to earth |
kV |
42 |
|
contact gap |
kV |
48 |
||
|
Control & Auxiliary Circuits |
kV |
2 |
||
|
1min Lightning Impulse Withstand Voltage |
phase to earth |
kV |
75 |
|
|
contact gap |
kV |
85 |
||
|
Rated short-time withstand current |
kA/s |
25,31.5,40/4 |
||
|
Rated peak withstand current |
kA |
63,80,100 |
||
|
Rated short-circuit breaking current |
kA |
25,31.5,40 |
||
|
Rated short-circuit closing current |
kA |
63,80,100 |
||
|
Circuit breaker life |
Time |
30 |
||
|
Rated operating sequence |
/ |
O-0.3s-CO-180s-CO |
||
|
Mechanical life |
Circuit breaker |
Times |
20000 |
|
|
lsolation/ground switch |
Times |
5000 |
||
|
Loop resistance |
1250A |
μΩ |
≤120 |
|
|
2500A |
μΩ |
≤80 |
||
|
3150A |
μΩ |
≤80 |
||
|
Rated filling pressure (gauge pressure at 20℃) |
MPa |
0.02 |
||
|
Annual gas leakage rate |
Years |
≤0.01% |
||
|
Insulating gas |
/ |
N2 |
||
|
Class of protection |
Compartment |
/ |
IP20 |
|
|
Gas box |
/ |
IP67 |
||
|
Cabinet |
/ |
IP41 |
||
|
Cabinet Impact Resistance (IK class) |
/ |
Ik10 |
||
|
Arc fault test (fault current/duration) |
kA/s |
31.5/1,40/0.5 |
||
Usage conditions
1. The ambient air temperature does not exceed 40°C, the 24-hour average does not exceed 35 ℃, and the minimum air temperature does not exceed 40°C
2. Altitude: ≤2000m
3. Humidity Relative humidity: daily average is not more than 95%, monthly average is not more than 90%; Water vapor pressure: the daily average is not more than 2.2Kpa, the monthly average is not more than 1.8Kpa
4. Seismic intensity: no more than 8 degrees, horizontal acceleration ≤0.4g, vertical acceleration ≤0.5g
5. Special conditions of use: When the switch cabinet is not normal use conditions, the user should negotiate with the manufacturer
Quality control
Strictly running quality control of XGN-12 SF6 gas insulated switchgear according to ISO9001, from supplier quality assurance-Incoming material -Incoming inspection-Qualified-Production-Process quality control-Final inspection-Qualified-In and out of storage-After-sales quality control

Hot Tags: xgn-12 sf6 gas insulated switchgear, China xgn-12 sf6 gas insulated switchgear manufacturers, suppliers, factory, gis rmu, gis switchgear, gis ring main unit, ring switch, inflatable ring main unit, rm6 ring main unit