Guidelines for Handling and Replacing Short-Circuit Faults in Power Capacitor Internal Capacitor Elements
Jul 11, 2025| Power capacitors, as indispensable reactive power compensation devices in power systems, play a significant role in improving power factor, enhancing voltage quality, and reducing line losses. However, during long-term operation, the internal capacitor elements of power capacitors may experience short-circuit faults due to various reasons, seriously affecting the performance and safe operation of the equipment. So, how should we deal with it?
I. Fault Feature Recognition and Emergency Handling
1. Typical manifestations of short-circuit faults:
The casing of the power capacitor is abnormally swollen or leaking oil.
An abnormal discharge sound is emitted during operation.
The temperature monitoring indicates localized overheating (ΔT > 15K);
The protection device frequently operates (overcurrent/imbalance protection).
2. Emergency Response Procedures:
① Immediately cut off the power supply of the circuit where the power capacitor is located.
② Activate the backup compensation circuit (if any)
③ Set up a safety isolation area (with a radius of no less than 5 meters)
④ Use an infrared thermal imager to confirm the location of the fault
II. Fault Component Detection Technology
1. Professional testing methods:
Capacitance value measurement (deviation of faulty phase > ±10%);
Dielectric loss test (tanδ value exceeds that of new product by 200%);
DC withstand voltage test (leakage current > 50μA at 2Un DC voltage).
2. Diagnostic Criteria:
It is considered as a component short circuit if it meets both of the following conditions:
① Insulation resistance < 100 MΩ (measured with a 2500V multimeter)
② The capacitance value has increased by more than 20%.