Ring Main Unit (RMU): Types, Working Principle and Applications

Nov 07, 2026|

1. What Is a Ring Main Unit (RMU)?

A Ring Main Unit (RMU) is a compact, factory-assembled medium-voltage (MV) switchgear system designed for power distribution networks. It integrates switching, isolation and protection functions within a metal-enclosed cabinet or modular assembly.

 

RMUs are commonly used in distribution systems operating at 12 kV, 24 kV and 33 kV, depending on the electrical network and project requirements.

The main components of an RMU typically include:

  •  Load Break Switch (LBS): Connects and disconnects circuits under normal load conditions.
  •  Circuit Breaker (CB): Interrupts normal operating currents and specified fault currents.
  •  Fuse-Switch Combination: Protects distribution transformers against short circuits and overcurrents.
  •  Earthing Switch: Grounds isolated circuits to ensure safety during maintenance.
  •  Busbars and Cable Terminations: Provide electrical connections between incoming and outgoing feeders.

 

Why Are RMUs Used in Power Distribution Networks?

In urban and rural distribution networks, electricity is delivered from primary substations to multiple secondary substations before reaching end users.

 

To improve power supply reliability, distribution networks are often designed in a ring configuration. This allows electricity to reach a distribution substation from two different directions.

 

Under normal operating conditions, many ring networks maintain a normally open point (NOP), operating in a radial configuration. When a cable fault or maintenance requirement occurs, the faulty section can be isolated and power restored through an alternative feeder.

 

RMUs play an essential role in this process by providing reliable feeder switching, circuit isolation and transformer protection.

 

2. Main Types of Ring Main Units

RMUs can be classified according to their insulation medium, structural design and installation environment.

 

2.1 Classification by Insulation Medium

A. Air-Insulated RMU (AIS RMU)

An air-insulated RMU uses atmospheric air as its primary insulation medium between live electrical components and grounded enclosures.

Main characteristics:

  •  Uses air instead of SF₆ gas for primary insulation.
  •  Generally adopts a compartmentalized structure.
  • Allows relatively straightforward inspection and maintenance, depending on the design.
  •  May require more installation space than compact gas-insulated designs.
  • Air-insulated RMUs are commonly used in industrial facilities, commercial buildings and medium-voltage distribution substations.

 

B. SF₆ Gas-Insulated RMU (GIS RMU)

An SF₆ gas-insulated RMU uses sulfur hexafluoride (SF₆) gas as an insulation medium. Depending on the switching technology, SF₆ may also provide arc-quenching functions.

 

Its main electrical components are installed inside a sealed gas compartment, allowing a compact design with high insulation performance.

Main characteristics:

  • Compact structure and small installation footprint.
  • Excellent dielectric and arc-quenching properties.
  •  Sealed compartments that protect internal components from external environmental influences.
  • Suitable for indoor substations and urban distribution networks.
  • Can support motorized operation and distribution automation.

 

SF₆ gas-insulated RMUs are widely used in urban power distribution, industrial parks, commercial complexes and infrastructure projects.

However, SF₆ has a high global warming potential. Proper gas handling, leakage management and recovery are therefore essential. SF₆-free alternatives using dry air and other insulation technologies are becoming increasingly important.

 

C. Solid-Insulated RMU

A solid-insulated RMU uses materials such as epoxy resin and insulating polymers as its primary insulation medium. Live electrical components are encapsulated or covered with solid dielectric materials.

 

Main characteristics:

  • Does not require SF₆ gas.
  • Compact and modular construction.
  • No gas leakage monitoring is required.
  • Suitable for environmentally conscious power distribution projects.

 

2.2 Classification by Structural Design

RMUs can also be divided into two common structural types:

  •  Common-Tank Type: Multiple switching components are integrated into a shared gas-filled enclosure, providing a compact design.
  •  Modular Type: Independent functional units are combined according to project requirements, allowing flexible configurations and potential system expansion.

 

2.3 Classification by Installation Environment

  • Indoor RMU: Designed for installation in electrical rooms, substations, factories and commercial buildings.
  •  Outdoor RMU: Equipped with weather-resistant enclosures for roadside substations, rural distribution networks and outdoor utility installations.

 

3. RMU Model Number Interpretation

RMU model numbers vary between manufacturers. A typical Chinese manufacturer model may follow a format such as:

 

XGW/N□-12 (F or F·R)/630-20

The symbols may indicate:

  •  X: Box-type structure.
  • G: Fixed-type switchgear.
  • W: Outdoor type.
  • N: Indoor type.
  •  F: Load break switch configuration.
  •  F·R: Load break switch and fuse combination.
  • 12: Rated voltage of 12 kV.
  • 630: Rated current of 630 A.
  • 20: Short-time withstand current of 20 kA, subject to the manufacturer's model definition.

 

These designations are manufacturer-specific rather than universal industry standards. Always refer to the relevant product documentation for accurate model interpretation.

 

4. RMU Working Principle and Main Components

A typical three-way RMU consists of two ring feeder units and one transformer protection unit.The two feeder units connect the substation to the incoming and outgoing medium-voltage cables, while the transformer feeder supplies power to the distribution transformer.

 

How Does an RMU Work?

1. Normal Operation: Incoming and outgoing feeders maintain the connection between neighboring distribution substations, while the transformer feeder supplies local electrical loads.

2. Fault Isolation: When a cable fault occurs, the relevant protection and switching devices isolate the faulty section.

3. Load Transfer: After the faulty section is safely isolated, operators can restore power through an alternative feeder.

4. Maintenance: The relevant circuit is disconnected, isolated and earthed before maintenance work begins.

 

Main Components of an RMU

1. Load Break Switch (LBS)

The load break switch makes and interrupts normal load currents and provides circuit isolation.

2. Circuit Breaker (CB)

Circuit breakers interrupt normal operating currents and specified fault currents. They are generally equipped with protection relays for overcurrent and earth-fault protection.

3. Fuse-Switch Combination

This configuration combines a load break switch with high-voltage current-limiting fuses to protect distribution transformers.

4. Earthing Switch

The earthing switch connects isolated electrical circuits to earth, helping ensure safe maintenance operations.

5. Busbars and Cable Compartments

Busbars connect different functional units, while cable compartments provide interfaces for incoming and outgoing medium-voltage cables.

6. Operating Mechanism and Control System

Modern RMUs can be equipped with motorized operating mechanisms, remote-control interfaces and intelligent monitoring systems to support distribution automation.

 

Why Are Three-Position Switches Used in RMUs?

Three-position load break switches are widely adopted in modern RMU designs. They provide three operating positions:

  • Closed: The circuit is connected.
  • Open: The circuit is disconnected.
  • Earthed: The isolated circuit is connected to earth.

This arrangement improves operational safety and helps prevent incorrect switching operations through mechanical interlocking.

 

5. Main Applications of RMUs

Ring Main Units are widely used in medium-voltage power distribution systems, particularly where compact dimensions and reliable power supply are required.Typical applications include:

  • Urban Power Distribution: Residential communities, shopping centers and office buildings.
  • Industrial Facilities: Manufacturing plants, factories and industrial parks.
  • Commercial Buildings: Hospitals, hotels and large commercial complexes.
  • Renewable Energy Projects: Solar power plants and other renewable energy installations.
  • Infrastructure Projects: Airports, railways, metro stations and data centers.
  • Rural Distribution Networks: Feeder interconnection and alternative power supply arrangements.

 

6. How to Select the Right RMU

When selecting a Ring Main Unit, engineers and project contractors should consider the following technical parameters:

 

ParameterKey Considerations
Rated voltage12 kV, 24 kV, 36 kV, etc.
Rated current630 A, 1250 A, etc.
Short-time withstand currentAccording to system short-circuit level
Insulation mediumAir, SF₆, solid insulation or dry air
Switching configurationLBS, CB or fuse-switch combination
Installation environmentIndoor or outdoor
Protection functionsOvercurrent, earth fault and transformer protection
AutomationManual or motorized operation, remote monitoring

 

For international projects, relevant IEC standards should also be considered, including IEC 62271-200 for AC metal-enclosed switchgear, IEC 62271-100 for circuit breakers and IEC 62271-105 for switch-fuse combinations.

 

Conclusion

Ring Main Units are essential components of modern medium-voltage power distribution networks. By integrating switching, isolation and protection functions into a compact assembly, RMUs provide reliable and flexible solutions for urban distribution networks, industrial facilities and infrastructure projects.With the development of smart grids and environmentally friendly technologies, modern RMUs are increasingly incorporating remote operation, intelligent monitoring, modular construction and SF₆-free insulation solutions.