JKWD5 Automatic Reactive Power Compensation Controller
✅Precise Reactive Power Control: Features dynamic response tracking and multiple customizable control modes to ensure optimal grid stability.
✅Energy Efficiency & Economic Benefits: Maximizes system efficiency and drastically reduces utility penalties by improving the power factor to above 0.95.
✅Flexible Compensation Architectures: Full compatibility with static, dynamic, and hybrid compensation systems to match various load profiles.
✅Advanced Human-Machine Interface (HMI): Equipped with an intuitive HMI for the real-time monitoring of power status, system parameters, and operating conditions.
✅Intelligent Self-Diagnosis: Automatically runs background diagnostics to detect operational issues and immediately trigger predictive alarms.
✅Comprehensive Protection Suite: Built-in safeguards against overvoltage, undervoltage, overcurrent, and overheating, paired with non-volatile event logging for seamless fault analysis.
- Product Introduction
The Jinneng Electric JKWD5 Automatic Reactive Power Compensation Controller is designed for low-voltage reactive power compensation systems in 400V distribution networks. It continuously monitors electrical parameters and automatically controls capacitor bank switching according to reactive power demand, helping maintain the power factor within the preset target range.
By coordinating with compatible switching devices, such as thyristor switches, contactors, or other supported capacitor switching devices, the JKWD5 enables automatic connection and disconnection of capacitor stages in response to changing load conditions. The specific switching method depends on the system configuration and the controller's output interface.
Product Features
Product Features
Dual Operation Modes: Supports both Power Factor Control and Reactive Power Control for maximum application flexibility.
Anti-Hunting Protection: Features advanced switching oscillation blocking in Power Factor mode to prevent rapid, repetitive capacitor cycling and extend equipment lifespan.
Automatic Polarity Detection: Automatically detects current signal polarity with exceptional precision and reliability, eliminating wiring errors during installation.
Intuitive User Interface: Designed with a user-friendly interface for streamlined operation and straightforward navigation.
Harmonic Monitoring & Protection: Equipped with real-time harmonic measurement capabilities and protective trip features to safeguard capacitor banks.
Fully Digital Parameters: All control thresholds and parameters are fully adjustable digitally for precise system tuning.
Dual Control Modes (Manual/Auto): Offers both manual and automatic operation modes to simplify installation, testing, and system commissioning.
Overvoltage Protection: Monitors system voltage and automatically disconnects capacitor banks during overvoltage events to prevent component damage.
Non-Volatile Memory Storage: Retains all programmed parameters permanently, ensuring settings are unaffected by power outages or system shutdowns.
Products Description
| Parameter | Specification |
| Product Model | JKWD5 |
| Product Type | Automatic Reactive Power Compensation Controller |
| Main Function | Reactive Power Compensation |
| Current Range | 0-5.5A |
| Rated Voltage | 230V Phase, 400V Line |
| Frequency | 50HZ |
| Output Contact Rating | 5A/220V/Loop |
| Measurement | Voltage/Current/Power Factor/ Reactive Power |
| Switching Control | Cyclic Switching for equal capacity stages; optimal switching for unequal-capacity stages |
| Communication | specify available interface/protocol and optional communication version |
| Operating Temperature | -25°C ~ +40°C |
| Humidity | ≤ 50% at 40°C, ≤ 90% at 20°C |
| Switch Control Mode | Cyclic switching (equal capacity), Optimal switching (unequal capacity) |
| Installation | Panel-mount |
| Customization | OEM/ODM availability to be confirmed separately |
Technical Specifications
| Category | Parameter | Factory default | Adjustment range |
| Engagement Factor | The controller considers engaging the capacitor bank when the system power factor falls below this threshold. | 0.98 | 0.70-0.90 |
| Disengagement Factor | The controller considers disengaging the capacitor bank when the system power factor exceeds this threshold. | 1.00 | 0.71-0.89 |
| Switching delay | Delay time from when the grid parameters allow capacitor engagement to the controller's actual engagement. | 30 seconds | 1-120 seconds |
| Distortion Threshold | If the system voltage distortion rate exceeds this threshold, the controller will gradually disengage all capacitor banks at 1 bank per second. | 5.0 | OFF-3.0-50.0% (Hysteresis: 2%) |
| Overvoltage Threshold | If the system voltage exceeds this threshold, the controller will gradually disengage all capacitor banks at 1 bank per second. | 450 / 260 | 410-480V (Hysteresis: 7V) / 236-277V (Hysteresis: 5V) |
| Output circuit | The controller has 12 output circuits, users can set 1~12 output circuit. | 12 | 1-12 |
| Reactive power mode | Select control mode. | OFF | OFF / ON |
| Main CT primary current | Primary current value of the current transformer for controller signal sampling. | 500 | 50-9000/5A |
| Shared Compensation Capacitance | Capacitance value for circuits 1-12 (subject to output circuit limits). | 30 | 0-80Kvar |
| PA-1 | MODBUS-RTU protocol address code. | 0 | 0-247 |
| PA-2 | Baud rate and communication. | 9600 | 1200-115200 |
| PA-3 | Communication parity check code. | oFF | OFF / odd / Even |
Application
✔ Industrial Plants – Compensates for heavy inductive loads (motors, transformers).
✔ Commercial Buildings – Reduces utility penalties and energy waste.
✔ Renewable Energy Systems – Balances reactive power in solar/wind farms.
✔ Data Centers – Ensures clean, efficient power delivery

Certifications
Quality and compliance are important considerations in electrical equipment selection. Jinneng provides relevant product documentation and certification information to support customer evaluation and project requirements.Available certificates, test reports, and technical documents can be provided for verification, subject to the specific product model and applicable standards.Please contact our team if you require certification documents or technical compliance information for your project.

FAQ
Do you offer OEM services for the JKWD5 Power Factor Controller?
+
-
OEM options may include product labeling, logo customization, and packaging, subject to the available customization scope and order requirements. Please contact our sales team to confirm availability, minimum order quantity, and lead time.
Do you provide ODM services for Power Factor Controller?
+
-
ODM requirements can be reviewed based on the requested functions, technical specifications, and product platform. Our team can evaluate the feasibility of your proposed customization and confirm the available options.
What information should I provide for an OEM or ODM inquiry?
+
-
Please provide your target market, intended application, required specifications, estimated order quantity, branding requirements, and any applicable certification requirements. Reference drawings or existing product specifications can also help us evaluate your request.
Can Power Factor Controller be used with harmonic filters?
+
-
The compatibility depends on the system configuration. In systems with significant harmonic distortion, the capacitor bank and harmonic conditions should be evaluated before selecting the compensation system.
How do I select an Power Factor regulator?
+
-
Selection should consider the system voltage, frequency, required compensation capacity, number of switching stages, current measurement method, target power factor and harmonic conditions.