JKWD5 Automatic Reactive Power Compensation Controller

✅Precise Reactive Power Control: Features dynamic response tracking and multiple customizable control modes to ensure optimal grid stability.
✅Energy Efficiency & Economic Benefits: Maximizes system efficiency and drastically reduces utility penalties by improving the power factor to above 0.95.
✅Flexible Compensation Architectures: Full compatibility with static, dynamic, and hybrid compensation systems to match various load profiles.
✅Advanced Human-Machine Interface (HMI): Equipped with an intuitive HMI for the real-time monitoring of power status, system parameters, and operating conditions.
✅Intelligent Self-Diagnosis: Automatically runs background diagnostics to detect operational issues and immediately trigger predictive alarms.
✅Comprehensive Protection Suite: Built-in safeguards against overvoltage, undervoltage, overcurrent, and overheating, paired with non-volatile event logging for seamless fault analysis.

  • Product Introduction

The Jinneng Electric JKWD5 Automatic Reactive Power Compensation Controller is designed for low-voltage reactive power compensation systems in 400V distribution networks. It continuously monitors electrical parameters and automatically controls capacitor bank switching according to reactive power demand, helping maintain the power factor within the preset target range.

By coordinating with compatible switching devices, such as thyristor switches, contactors, or other supported capacitor switching devices, the JKWD5 enables automatic connection and disconnection of capacitor stages in response to changing load conditions. The specific switching method depends on the system configuration and the controller's output interface.

 

Product Features

 

Product Features
 

Dual Operation Modes: Supports both Power Factor Control and Reactive Power Control for maximum application flexibility.

 

Anti-Hunting Protection: Features advanced switching oscillation blocking in Power Factor mode to prevent rapid, repetitive capacitor cycling and extend equipment lifespan.

 

Automatic Polarity Detection: Automatically detects current signal polarity with exceptional precision and reliability, eliminating wiring errors during installation.

 

Intuitive User Interface: Designed with a user-friendly interface for streamlined operation and straightforward navigation.

 

Harmonic Monitoring & Protection: Equipped with real-time harmonic measurement capabilities and protective trip features to safeguard capacitor banks.

 

Fully Digital Parameters: All control thresholds and parameters are fully adjustable digitally for precise system tuning.

 

Dual Control Modes (Manual/Auto): Offers both manual and automatic operation modes to simplify installation, testing, and system commissioning.

 

Overvoltage Protection: Monitors system voltage and automatically disconnects capacitor banks during overvoltage events to prevent component damage.

 

Non-Volatile Memory Storage: Retains all programmed parameters permanently, ensuring settings are unaffected by power outages or system shutdowns.

 

Products Description

 

ParameterSpecification
Product ModelJKWD5
Product TypeAutomatic Reactive Power Compensation Controller
Main FunctionReactive Power Compensation
Current Range0-5.5A
Rated Voltage230V Phase, 400V Line
Frequency50HZ
Output Contact Rating5A/220V/Loop
MeasurementVoltage/Current/Power Factor/ Reactive Power
Switching ControlCyclic Switching for equal capacity stages; optimal switching for unequal-capacity stages
Communicationspecify available interface/protocol and optional communication version
Operating Temperature-25°C ~ +40°C
Humidity≤ 50% at 40°C, ≤ 90% at 20°C
Switch Control ModeCyclic switching (equal capacity), Optimal switching (unequal capacity)
InstallationPanel-mount
CustomizationOEM/ODM availability to be confirmed separately

 

Technical Specifications

 

CategoryParameterFactory defaultAdjustment range
Engagement FactorThe controller considers engaging the capacitor bank when the system power factor falls below this threshold.0.980.70-0.90
Disengagement FactorThe controller considers disengaging the capacitor bank when the system power factor exceeds this threshold.1.000.71-0.89
Switching delayDelay time from when the grid parameters allow capacitor engagement to the controller's actual engagement.30 seconds1-120 seconds
Distortion ThresholdIf the system voltage distortion rate exceeds this threshold, the controller will gradually disengage all capacitor banks at 1 bank per second.5.0OFF-3.0-50.0% (Hysteresis: 2%)
Overvoltage ThresholdIf the system voltage exceeds this threshold, the controller will gradually disengage all capacitor banks at 1 bank per second.450 / 260410-480V (Hysteresis: 7V) / 236-277V (Hysteresis: 5V)
Output circuitThe controller has 12 output circuits, users can set 1~12 output circuit.121-12
Reactive power modeSelect control mode.OFFOFF / ON
Main CT primary currentPrimary current value of the current transformer for controller signal sampling.50050-9000/5A
Shared Compensation CapacitanceCapacitance value for circuits 1-12 (subject to output circuit limits).300-80Kvar
PA-1MODBUS-RTU protocol address code.00-247
PA-2Baud rate and communication.96001200-115200
PA-3Communication parity check code.oFFOFF / odd / Even

 

Application

 

✔ Industrial Plants – Compensates for heavy inductive loads (motors, transformers).
✔ Commercial Buildings – Reduces utility penalties and energy waste.
✔ Renewable Energy Systems – Balances reactive power in solar/wind farms.
✔ Data Centers – Ensures clean, efficient power delivery

 

product-2126-1134

 

Certifications

 

Quality and compliance are important considerations in electrical equipment selection. Jinneng provides relevant product documentation and certification information to support customer evaluation and project requirements.Available certificates, test reports, and technical documents can be provided for verification, subject to the specific product model and applicable standards.Please contact our team if you require certification documents or technical compliance information for your project.

Certificate

 

 

FAQ

Do you offer OEM services for the JKWD5 Power Factor Controller?

+

-

OEM options may include product labeling, logo customization, and packaging, subject to the available customization scope and order requirements. Please contact our sales team to confirm availability, minimum order quantity, and lead time.

Do you provide ODM services for Power Factor Controller?

+

-

ODM requirements can be reviewed based on the requested functions, technical specifications, and product platform. Our team can evaluate the feasibility of your proposed customization and confirm the available options.

What information should I provide for an OEM or ODM inquiry?

+

-

Please provide your target market, intended application, required specifications, estimated order quantity, branding requirements, and any applicable certification requirements. Reference drawings or existing product specifications can also help us evaluate your request.

Can Power Factor Controller be used with harmonic filters?

+

-

The compatibility depends on the system configuration. In systems with significant harmonic distortion, the capacitor bank and harmonic conditions should be evaluated before selecting the compensation system.

How do I select an Power Factor regulator?

+

-

Selection should consider the system voltage, frequency, required compensation capacity, number of switching stages, current measurement method, target power factor and harmonic conditions.

 

Hot Tags: jkwd5 automatic reactive power compensation controller, China jkwd5 automatic reactive power compensation controller manufacturers, suppliers, factory, svc reactive power compensation, current controller, rs232 controller, , , power controller