Cold Shrink Cable Termination Kits

✅ IEC 60502-4:2023 type test reports available (Wuhan High Voltage Testing Institute) ✅ Approved supplier for State Grid & China Southern Power Grid ✅ Premium Liquid Silicone Rubber ✅ Passed full dielectric & partial discharge tests with ample insulation margin. ✅ 10+ years of experience, custom process available for site conditions

  • Product Introduction
Cold shrink cable termination kits are medium voltage cable accessories for indoor and outdoor applications. We offer 3 voltage classes: 8.7/15kV (10kV class), 12/20kV (20kV class), 26/35kV (35kV class). Indoor type is designed for dry indoor conditions. Outdoor type comes with extended & larger sheds to resist sunlight, rain and wind for outdoor service.
Parameter10 kV Class
8.7/15 kV · Um 17.5 kV
20 kV Class
12/20 kV · Um 24 kV
35 kV Class
26/35 kV · Um 42 kV
Rated voltage U0/U8.7/15 kV12/20 kV26/35 kV
Highest voltage for equipment, Um17.5 kV24 kV42 kV
Typical applicationDistribution networks and industrial plants - the highest-volume size.20 kV distribution systems, wind farms and mining networks.35 kV transmission, large industrial parks and substation connections.

Models
N = indoor 

W = outdoor

NLS-10 / WLS-10NLS-20 / WLS-20NLS-35 / WLS-35
Cable cross-section, mm²
by section group

1. 25–50
2. 70–120
3. 150–240
4. 300–400

5. 500-630

1. 35–70
2. 95–185
3. 240–400
4. 500–800
1. 50–95
2. 120–240
3. 300–400
4. 500–800
Section group code1–41–41–4
Applicable cable cores1-core, 2-core, 3-core, 4-core, 5-core1-core, 2-core, 3-core, 4-core, 5-core1-core, 2-core, 3-core, 4-core, 5-core

 

 

Model Meaning

 

cold shrink termination kit

  1. "NLS-10/3.2" means the 10kV cold shrink cable outdoor/indoor terminal, which is suitable for three-core cables with a cross-section of 70–120mm².
  2. "JSY-35/1.3" means the 35kV cold shrink cable accessory intermediate joint, which is suitable for single-core cables with a cross-section of 300–400mm².
Voltage code:
CodeClassRated voltage
1LV0.6/1.0 kV
1010 kV6/10 · 8.7/15 kV
2020 kV12/20 · 18/20 kV
3535 kV21/35 · 26/35 kV

 

Components in Kits

 

10kV 3-Core Outdoor Cold Shrink Cable Termination Kits

IEC Cold Shrink Cable Termination Kits

Kit Includes: • Cold‑shrink main insulation tube • Stress‑control tube • Earth connection strap • Mastic sealing compound • PVC insulating tape • Installation instruction manual • Lug is optional

 

Products Advantages

 

Advantages of our Cold Shrink Cable Termination Kits:

  1. Premium Material:Conductive and insulating layers are made of high-grade liquid silicone rubber. Excellent shrinkage performance, great aging resistance, tear resistance, good elasticity and strong clamping force, ensuring stable long-term operation.
  2. Superior Appearance Quality:Smooth glossy surface, flat parting lines, sufficient raw material input.
  3. Reliable Electrical Performance:Full tests including voltage withstand, thermal cycling and partial discharge are completed. Higher insulation margin with sufficient safety redundancy complying with national standards.
  4. Certification:IEC type test reports issued by Wuhan High Voltage Testing Institute-new name CEPRI 
  5. Qualified Supplier:Approved supplier for State Grid and China Southern Power Grid.
  6. Rich Technical Experience: More than 10 years of technical accumulation. Customized production process available according to project site conditions.
  7. High-quality Production Equipment:Equipped with well-known domestic brand production machines.
  8. Shelf Life: 2 years storage.

 

Products Details

 

Cold Shrink Cable Termination Kits details

  • Thickness & weight: Thicker wall, heavier than competitors, high safety margin.       
  • Toughness: Highly flexible, no cracking when bent or twist, tear-resistant, aging-resistant, and highly elastic       
  • Smoth surface: Glossy, void-free moulded surface,straight out of the mould, no polishing.(Before expansion and after expansion)
  • Flush seam: Seam flush to surface, no burr or step or mini gap, flat and smooth
  • Semi-conductive layer: Built-in semi-conductive layer for stress control

     

Test Report

 

Thirteen type tests performed by CEPRI in compliance with GB/T 12706.4-2020 and IEC 60502-4:2023.

TestRequirementResult
Ac Withstand VoltageNo Breakdown At 39 kV, 5 MinPassed
Dc Withstand VoltageNo Breakdown At 35 kV, 15 MinPassed
Partial Discharge, Ambient≤ 10 Pc At 15 kV2.0 Pc, All Phases
Partial Discharge, 95–100 °c≤ 10 Pc At 15 kV1.7 Pc, All Phases
Lightning Impulse95 Kv, 10 Positive + 10 Negative At 95–100 °cPassed
Thermal Cycle, In Air60 Cycles, 22 Kv, Conductor 95–100 °cPassed
Thermal Short Circuit, Screen3.5 Ka, 1 S, Twice3.51 / 3.52 Ka, 1.04 S
Thermal Short Circuit, Conductor50 Ka, 2 S, Twice52.09 / 52.15 Ka, 2.00 S
Dynamic Short Circuit177 Ka, At Least 10 Ms178.84 Ka, 13.0 Ms
Humidity Indoor11 kV, 300 HPassed
Ac Withstand Under Rain Outdoor35 kV, 1 MinPassed
Salt Fog Outdoor11 kV, 1000 HPassed
Immersion Outdoor10 Cycles In Water, 95–100 °cPassed

WPS3

 

Application

 

Cold Shrink Cable Termination Kits

● Underground Cable Terminations (joints, transformers, switchgear)

● Overhead Line Transitions (pole-mounted terminations)

● Industrial Plants (mining, oil & gas, chemical plants)

● Renewable Energy (solar farms, wind turbines)

● Railway & Metro Power Distribution

 

product-750-500

 

Factory 

 

We hold multiple authoritative certifications-ISO three-system, CCC, CQC, CE, and IEC, every product undergoes routine factory inspection and type testing. Each process is strictly controlled-precision craftsmanship for dependable quality-ensuring product stability and reliability from the very source.

 

Jinneng/Haneng is equipped with a full range of production and testing facilities compliant with national (GB) and IEC standards, with in-house electrical safety testing capabilities. We operate a 300 kV high-voltage hall and five major test zones, capable of conducting withstand voltage, partial discharge, lightning impulse, aging, high/low temperature, salt spray, voltage cycling test, glow wire tests, and others.

 

Jinneng factory and experiment area

 

FAQ

 

  • Q: Can we get samples for testing? 

    A: Yes, 1–2 sets of samples can be free upon assessment, while the freight cost shall be borne by the buyer.

     

  • Q: What is your MOQ? 

    A: Our minimum order quantity is 100 sets, trial order is acceptable.

     

  • Q: How long is your production lead time? 

    A: 15–30 working days, depending on item types and order quantity.

     

  • Q: What are your FOB ports? 

    A: FOB Shanghai / Ningbo / Guangzhou. Extra inland freight will be charged for other ports.

     

  • Q: What is your product warranty period? 

    A: 12 months from the date of shipment, longer warranty period, higher price.

     

  • Q: Cold shrink or heat shrink - which should I choose?

    A: Choose cold shrink for confined spaces or sites where hot work is banned. Heat shrink works for ≤1kV applications, or when certified installers with hot-work permits are available and low upfront cost is your priority.

     -Fire & permits: Cold shrink requires no flame or heat gun, no hot-work permit for tunnels, switch rooms, hazardous zones. Heat shrink needs hot work approval.

     -Interface pressure: Cold shrink's pressure is factory preset. Heat shrink's pressure depends on installer heating technique, leading to inconsistent results.

     -Low temperature: Silicone cold shrink keeps elasticity under 0°C. Polyolefin heat shrink is hard to shrink evenly in freezing weather.

    -Shelf life: Cold shrink: normally 2–3 years (pre-expanded). Heat shrink has a much longer shelf life.

     

7.Q: How do I match the cross-section and core count?

    A: Read the model code from left to right - voltage class, section group, core count. NLS-10/3.2 means a cold-shrink indoor termination for 10 kV, section group 3 (150–240 mm²), 2-core.

    -10 kV (8.7/15 kV). Group 1 = 25–50 mm², 2 = 70–120, 3 = 150–240, 4 = 300–400, 5 = 500~630.

    -20 kV (12/20 kV). Group 1 = 35–70 mm², 2 = 95–185, 3 = 240–400, 4 = 500–800.

    -35 kV (26/35 kV). Group 1 = 50–95 mm², 2 = 120–240, 3 = 300–400, 4 = 500–800.

    -Core count. One-core and three-core are the standard configurations. A three-core kit includes the breakout plus three phase terminations.

 

 