1kV 10kV 35kV Indoor Heat Shrink Termination Kit
✅Excellent Sealing and Moisture Resistance
✅High Dielectric Strength and Stable Insulation Resistance
✅Good Mechanical Protection
✅Strong Adaptability and Wide Application
✅Relatively Simple Installation and High Efficiency
✅Compact Size, Saves Space
- Product Introduction
1kV 10kV 35kV indoor heat shrink termination kit refers to a complete cable termination assembly formed by using various components made of heat-shrinkable materials (such as radiation-cross-linked polyolefin), like tubes, branch-offs, and sheds.
These components are heated and shrunk to tightly wrap around the cable end and its connection point (to a switch or transformer terminal). This process restores insulation, provides sealing, offers mechanical protection, and improves electric field distribution.
Main Components
● Stress Control Tube/Tape/Gel:It is used to dissipate the concentrated electrical stress at the cut-off point of the cable shield
● Heat-Shrink Insulation Tube:It is the core component ensuring electrical safety.
● Heat-Shrink Seal Tube:Used for the outermost sealing of the termination, preventing moisture ingress, and also for filling voids between cable cores.
● Heat-Shrink Breakout:Used for multi-core cables (e.g., three-core cables) to separate the individual cores and provide sealing for the cable body.
● Lug/Terminal:Crimped onto the cable conductor for connecting to the terminal stud of switchgear or transformers.
● Phase Identification Tube:Sleeved over each phase's insulation tube to identify phases A (Yellow), B (Green), and C (Red) for easy recognition.

Products Description
| Parameter | 1kV (Low Voltage) | 10kV (Medium Voltage) | 35kV (Medium-High Voltage) |
|---|---|---|---|
| Rated U₀/U | 0.6/1 kV | 8.7/10 kV | 26/35 kV |
| Applicable Cable | single/3-core, Cu/Al conductor, XLPE insulation | Same, with copper tape/wire shield | Same, enhanced shielding & thicker insulation |
| Conductor Cross-section | 16–400 mm² | 25–400 mm² | 50–800 mm² |
| Shrink Temperature | 110–140°C | 110–140°C | 110–140°C |
| Operating Temp Range | -50°C to 90°C | -50°C to 90°C | -50°C to 90°C |
| Test Withstand Voltage | 3 kV/5 min | 30 kV/1 min | 95 kV/1 min |
| Compliance Standard | GB11033, IEC 62076 | Same, plus DL/T 859 | Same, stricter partial discharge (<10 pC) |
Product Models
Below table is 10kV and 20kV for reference:
| Product Name | Image | Model Specification | Applicable Cable Cross-Section (mm²) |
|---|---|---|---|
| 10kV Single-Core Heat-Shrink indoor Termination |
|
NSY-10/1.1 | 25~50 |
| NSY-10/1.2 | 70~120 | ||
| NSY-10/1.3 | 150~240 | ||
| NSY-10/1.4 | 300~500 | ||
| 10kV Three-Core Heat-Shrink indoor Termination |
|
NSY-10/3.1 | 25~50 |
| NSY-10/3.2 | 70~120 | ||
| NSY-10/3.3 | 150~240 | ||
| NSY-10/3.4 | 300~500 | ||
| 20kV Single-Core Heat-Shrink indoor Termination |
|
NSY-20/1.1 | 50~95 |
| NSY-20/1.2 | 120~240 | ||
| NSY-20/1.3 | 300~400 | ||
| NSY-20/1.4 | 500~800 | ||
| 20kV Three-Core Heat-Shrink indoor Termination |
|
NSY-20/3.1 | 50~95 |
| NSY-20/3.2 | 120~240 | ||
| NSY-20/3.3 | 300~400 | ||
| NSY-20/3.4 | 500~800 |
For more models info,pls contact us
Applications
Voltage Level: Commonly used for medium and low-voltage power cables, up to 35kV.
Environment: Specifically designed for indoor environments,
such as:
● Distribution rooms, switchgear stations
● Cable basements, cable floors in buildings
● Equipment connections within factory workshops
● Any indoor location not exposed to direct sunlight, rain, snow, or direct chemical corrosion.

Installation step
1. Preparation: Strip the cable's outer sheath, steel armor, inner sheath, and shield layer to expose a specified length of conductor.
Strictly follow the 2. stripping dimensions provided in the termination kit's installation manual.
3. Install Ground Wire: Fix the ground wire to the steel armor and copper shield.
4. Install Breakout: Slide the heat-shrink breakout onto the cable trifurcation area. Heat and shrink it from the center outwards until it tightly wraps the cable.
5. Install Stress Control Tube: This is a critical step. Slide the stress control tube over the cut-off point of the shield layer on each phase. Heat and shrink it.
6. Install Lug: Crimp the lug onto the cable conductor.
7. Install Insulation Tube: Slide the insulation tube over each core, covering the stress control tube and part of the original insulation. Heat and shrink it.
8. Install Seal Tube and Phase Tubes: Install the seal tube and phase identification tubes on the outermost layer to complete the sealing and identification.
9. Connect to Equipment: Secure the finished termination head to the terminal of the switchgear or transformer.